Liebert GXT5-5000IRT5UXLN P/N 01201973
Liebert GXT5-5000IRT5UXLN 
P/N 01201973

Ratings (VA/W ) 5000 VA / 5000 W 
Dimensions and weight
Dimensions (mm) Unit, W×D×H 430×630×217
Unit weight (kg) 70.8 
Input AC Parameters
Operating Frequency, Nom 60 Hz (Factory Default is 50 Hz )
Factory Default Voltage 230 VAC
User-configurable Voltage 200/208/220/230/240 VAC
Operating Voltage Range without battery operation 176 to 288 VAC 
(100 to 176 VAC with power derating)
Maximum allowable Voltage 288 VAC
Input frequency without battery operation 40 to 70 Hz
Output AC Parameters
AC-AC Efficiency 94% 
Factory Default Voltage 230 VAC
Frequency 50 Hz or 60 Hz, Nominal
Waveform Pure Sinewave
Output Power Connection Output terminal block
Main Mode Overload >150% minimum 200 ms, 125 – 150% for 60 seconds; 
105 – 125% for 5 minutes; ≤ 105% continuous
Internal Battery
Charger Current 2.25 A (default), maximum 5 A 
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 2 x 8 x 12V x 9.0 AH
Back-up Time at Full Load 7
Back-up Time at Half Load 19 
Bypass Protection Limits
Upper-limit selections + 10%, + 15%, + 20%; default + 10%.
Lower-limit selections - 10%, - 15%, - 20%; default - 15%
Disable-bypass operation When the input frequency prevents synchronous operation
General
Operating Temperature, °C Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature, °C - 15 to + 40
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 )
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A
Transportation ISTA Procedure 1E
Extended Run Rack/Tower, Rail Kit Bundled,
Web Card (RDU101) bundled, Integrated Maintenance Bypass
3 Yrs On Site Replacement + Free Startup, not include rural area and Pattani, Ya-La, Narathiwas